Ask how much water an AI response consumes, and you will find some strikingly different estimates. A 2023 study suggested that running GPT-3 could consume the equivalent of a 500 ml bottle of water for every 10 to 50 responses. Google, in its 2025 study, estimated that a median Gemini text prompt uses just 0.26 ml, or about five drops. The difference is dramatic, but so are the methodologies behind these numbers. So, what explains this gap, and what does it tell us about the actual water footprint of AI?
The truth, as is often the case, lies somewhere between the headlines. Data centres do consume substantial amounts of water, much of it used to cool the servers that power our digital lives. Every AI response, video stream and UPI payment runs on infrastructure that converts electricity into heat, and keeping that heat under control can require significant volumes of water.
The International Energy Agency (IEA) estimates that data centres consume more than 560 billion litres of water annually, a figure that could reach approximately 1,200 billion litres by 2030 (Engineers Ireland, citing IEA). As AI adoption accelerates and data centre capacity expands, the industry’s water footprint is attracting growing scrutiny.
But the numbers tell only part of the story. The impact of water consumption depends heavily on where a facility is located, the water sources it relies on, the cooling technology it uses and the conditions of the surrounding watershed. A data centre operating in a water-abundant region has a very different footprint from one drawing on scarce freshwater in a water-stressed basin during a dry summer.
The headline figures reveal only part of the picture. The wide variation in estimates of water consumed per AI prompt reflects differences in measurement and methodology, while the response of data centre operators, particularly in India, highlights the growing focus on managing water use more responsibly.
Let’s separate the reality from the myth, examine what the major studies actually measure, look at what Indian operators have disclosed over the past three years and explore where water consumption has raised legitimate concerns and how the industry is responding.
How a data centre actually uses water
A data centre’s water footprint goes beyond what you see inside the facility. In fact, it has three parts, and surprisingly, the biggest share may not come from the data centre itself.
- On-site cooling (scope 1): Servers turn almost all their electricity into heat. Many large sites reject that heat through cooling towers, where water evaporates and carries the heat away. About 70 to 80% of the water entering a cooling tower is consumed; the rest flushes out minerals (The Register).
- Electricity generation (scope 2): Coal, gas, nuclear and hydro plants also lose water. Of the IEA’s 560 billion litres for 2023, about 373 billion litres came from power generation and 140 billion litres from direct cooling (Daily Maverick, citing IEA). The remaining ~47 billion litres sits in hardware manufacturing.
- Chips and servers (scope 3): Semiconductor fabs use large volumes of ultra-pure water before a server ever reaches the data hall (EESI).
Withdrawal is not consumption: The distinction is important. Water withdrawal is the total volume of water drawn from a utility, river or borewell. Water consumption is the portion that is not returned to the source, because it evaporates or otherwise leaves the basin. As explained in Balancing Bits and Drops (arXiv, 2026), the two measures are not interchangeable. Yet many alarming headlines cite withdrawal figures as though every litre drawn is permanently lost
WUE is the scorecard: Water Usage Effectiveness is litres of water consumed per kWh of IT energy, defined in ISO/IEC 30134-9:2022; lower is better (Stanford SURJ). The best hyperscale fleets now report well under 0.5 L/kWh, as the next section shows.
Water and power trade off: Evaporative cooling saves electricity. Google says water cooling can cut data centre energy use by roughly 10% compared with air cooling in some regions (WaterWorld). So a ‘zero-water’ site can raise power use, and with it the water used at the power plant.
Reading between the lines
The reports broadly tell us two things: Data centres are using more and more water and a large part of that water footprint actually comes from outside the facility. Operators may be getting better at using water efficiently, but overall consumption is still going up because data centres are expanding even faster.
| Document | Published | What it found on water |
|---|---|---|
| 2024 United States Data Center Energy Usage Report (Lawrence Berkeley National Laboratory, for the US Congress) | Dec 2024 | US data centres consumed 66 billion litres directly in 2023, up from 21.2 billion in 2014; 84% of it in hyperscale sites. Hyperscalers alone may use 60 to 124 billion litres by 2028 (DCD). Electricity for those sites consumed nearly 800 billion litres more (TechTarget). |
| Energy and AI (IEA) | Apr 2025 | About 560 billion litres worldwide in 2023, roughly two-thirds of it from power generation (Daily Maverick), possibly rising to about 1,200 billion by 2030 (Engineers Ireland). |
| Rystad Energy analysis | Aug 2026 | Direct cooling used about 222 billion litres in 2025 and could reach 644 billion by 2030; aggressive water saving could hold it to 388 billion (Down To Earth). |
| Making AI Less “Thirsty” (UC Riverside, UT Arlington) | 2023; CACM 2025 | Training GPT-3 in Microsoft’s US data centres used about 700,000 litres on site and 5.4 million litres including power-plant water. The paper excludes hardware manufacturing. |
| Google, Measuring the Environmental Impact of Delivering AI at Google Scale | Aug 2025 | A median Gemini text prompt uses 0.24 Wh and 0.26 ml of water (The New Stack). The water figure counts on-site cooling only (Neowin). |
| Google 2026 Environmental Report (calendar 2025) | Jun 2026 | Water consumption rose 34% to 10.9 billion gallons, about 41 billion litres (The Heart of Tech). Replenishment projects returned 7.7 billion gallons, 78% of freshwater consumption (Trellis). |
| Microsoft water update (fiscal 2025) | Jun 2026 | Claims it replenished more water than it used; 90% of its fleet uses low- or zero-water cooling; 25% better water efficiency than 2022 (Facilities Dive). |
| Meta 2025 Environmental Data Index (calendar 2024) | Sep 2025 | 2,974 megalitres consumed directly by data centres, against 72,207 megalitres embedded in purchased electricity (TechTarget). |
| Amazon water spotlight (AWS) | 2026 | WUE of 0.12 L/kWh, which AWS calls seven times better than the industry average; 75% of the way to its 2030 water-positive goal in 2025, up from 53% in 2024. In 2024 its WUE was 0.15 L/kWh, 40% better than 2021 (AWS). |
Meta’s numbers show the scale gap plainly: the water behind its electricity was about 24 times its on-site data centre water.
Myth vs reality: seven popular claims, checked
Viral claims tend to swing between two extremes. Some overstate how much water a single AI prompt consumes, while others underplay the cumulative impact of an entire data centre. The reality lies somewhere in between: the water use may be small with each click, but it adds up at scale. And its actual impact depends greatly on where the data centre is located.
| The claim | Verdict | What the evidence says |
|---|---|---|
| ‘Every ChatGPT chat drinks a bottle of water. | Exaggerated | The 500 ml per 10 to 50 replies came from a 2023 GPT-3 estimate; its US average was about 17 ml per reply, 87% of it power-plant water (Making AI Less ‘Thirsty”). Google measured 0.26 ml on site for a median Gemini prompt in 2025. Adding power-plant water at the US average of about 4.5 L/kWh for its 0.24 Wh gives roughly 1.3 ml in total: about 25 drops, not a bottle. |
| ‘Google’s ‘five drops’ settles it.’ | Accurate but partial | The figure counts only on-site cooling. Experts including Shaolei Ren and Alex de Vries-Gao say it omits power-plant water (Neowin), which on our estimate above is about four times the on-site share. |
| ‘Data centres are draining the planet’s water.’ | Myth globally, real locally | All US data centres together directly used water equal to roughly 160,000 American households in 2023 (MOST Policy Initiative). Yet in The Dalles, Oregon, Google’s sites used 29% of the city’s water in 2021 (The Oregonian via WaterWatch). |
| ‘The water just goes back into the system.’ | Myth | Up to 85% of the water data centres use evaporates and does not return to the local supply (MOST Policy Initiative). |
| ‘Air cooling makes a data centre water-free.’ | Half-true | Dry cooling saves about 2.15 litres per kWh of IT load but adds 0.30 to 0.74 kWh of electricity (Rystad via Down To Earth). Indian coal plants may use up to 3.5 m³ of water per MWh, and almost half of surveyed capacity has broken even that norm (Down To Earth, citing CSE). On such a grid, the extra power claws back a large part of the saving. |
| ‘Water-positive pledges mean no local harm.’ | Partly myth | Replenishment projects often sit in other watersheds. IEEFA’s Labanya Prakash Jena says such offsets don’t fix depletion where the data centres actually operate (Down To Earth). |
| ‘India’s data centres use 150 billion litres a year.’ | Unverified, likely overstated | The figure traces to market researcher Mordor Intelligence (CEEW). The five largest operators, with 70 to 75% of capacity (ICRA), disclosed about 1.6 billion litres between them in their latest reports (next section). Even adding power-plant water for ~8 TWh of electricity, our rough total is nearer 40 billion litres. |
The last row matters most for India. The honest answer is that nobody knows the national number, because no rule makes operators publish complete, site-level data.
India: what operators reported over the last three years
India’s major data centre operators paint a fairly encouraging picture, with on-site water use generally remaining modest and, in several cases, declining over time. But there is a catch: some report water withdrawal, others report consumption and few break the numbers down by individual data centre. So, while the available figures offer useful insights, they still leave us with an incomplete picture of how much water these facilities actually use, and where that use has the greatest impact.
India had about 1.8 GW of live IT capacity by mid-2026, after adding 258 MW in the first half of the year; Savills expects more than 7 GW by 2030 (Savills via The Realty Today). Mumbai held 52% of capacity and Chennai 21% in early 2025 (JLL), and both cities face chronic water stress.
| Operator | Live IT capacity | What it reports | Last three reported years | What it tells us |
|---|---|---|---|---|
| Sify (incl. Sify Infinit Spaces) | 192 MW, 14 sites (FY26) | Withdrawal, whole company | FY24: 6,132,323 kL · FY25: 306,916 kL · FY26: 285,902 kL | Falling. The 20-fold drop from FY24 to FY25 is not explained in the report (Sify SR 2024-25). |
| STT GDC India | 400+ MW incl. under construction, 30+ sites | India withdrawal and WUE | 2023: 419,204 kL · FY24: no India figure · FY25: 298,595 kL | Best disclosure of the group, assured by DNV, with a yearly WUE series (charted below). |
| CtrlS | Not given | Consumption | FY23: 468,330 kL · FY24: 409,037 kL · FY25: not published | Down 13%; says moving to air-cooled systems saves 119,662 kL a year. |
| Nxtra by Airtel | 220 MW, 14+ core and 120+ edge sites | Withdrawal and consumption | FY23, FY24: not disclosed · FY25: 201,028 kL withdrawn, 216,357 kL consumed | No trend possible. Consumption exceeds withdrawal, unexplained. |
| NTT GDC India | Not given | Withdrawal and consumption | 2023: 413,779 kL withdrawn, 203,297 kL consumed · 2025 report: no figures | Reporting stopped. |
| AdaniConneX | Not given | Nothing data-centre specific | Parent Adani Enterprises withdrew 4,390 million litres in 2025 across all businesses | Cannot be separated. |
| Yotta (Greater Noida) | 30 MW live | No ESG report | Company says about 60 lakh litres a year of treated non-potable water for cooling (Down To Earth) | Unverified. |
CtrlS, NTT and AdaniConneX figures are as compiled by Down To Earth (Nov 2025). Where a trend is visible, it points down: Sify’s withdrawal fell 7% in FY26 while its energy use rose 16%.

Sify IR 2025-26; Nxtra SR 2025; Down To Earth (rule of thumb, Yotta); CEEW via Analytics India Magazine · our calculation
The widely repeated 26 million litres per MW may suit an evaporative hyperscale site at full load. It does not describe the air-cooled co-location sites that Indian operators actually report on.
A rough national check: The five largest operators hold 70 to 75% of India’s capacity (ICRA). Their latest figures add up to about 1.6 billion litres, so national on-site use is probably 2 to 3 billion litres a year. Power plants likely add far more. Data centres used about 0.5% of India’s electricity in 2024 (CEEW), roughly 8 TWh of the 1,623 TWh consumed in 2023-24 (Down To Earth). At the US grid average of about 4.5 litres per kWh (LBNL’s 800 billion litres over 176 TWh, via TechTarget), that is roughly 36 billion litres. These are our own order-of-magnitude estimates from mixed years and metrics.
So, as worldwide, most of India’s data centre water is hidden in the grid, not the cooling tower. CEEW still expects total use to more than double by 2030 (Analytics India Magazine).
The impact: Water stress on the ground
Data centres have not caused a national water crisis anywhere. They have repeatedly sharpened local ones, especially where approvals never asked how much water a site would use.
| When | Where | What happened |
|---|---|---|
| Sep 2026 | Visakhapatnam, Andhra Pradesh | Clearance papers show Google’s AI hub approved for 2.51 GW, more than double the 1 GW announced, in nine days and without a public hearing. One site sits metres from a drinking-water reservoir. Google says the campus will be air-cooled and will not touch drinking water; petitions are pending before the NGT and the High Court (The Next Web, citing the Guardian). |
| Aug 2026 | Karnataka | The state data centre policy promises sites uninterrupted water 24/7, without saying who gives way in a shortage. Bengaluru gets about 2,000 MLD from the Cauvery against demand that can reach 3,000 MLD (Down To Earth). |
| May 2026 | Visakhapatnam, Andhra Pradesh | The clearance for the 1 GW Tarluvada park does not state operational water use or its source. The district has the lowest available groundwater in the state. EIA rules have no data centre category, so no public hearing was needed (Mongabay-India via Scroll). |
| Apr 2026 | Urban India | Municipal supply covers only 30 to 60% of demand at most city data centre sites; private tankers fill the gap, and groundwater met 20 to 40% at some older facilities. Water is under 2% of operating cost, so there is little price signal to save it (Analytics India Magazine). |
| Nov 2025 | Tusiana, Greater Noida, Uttar Pradesh | Villagers beside the Yotta park say the water table has fallen from 20–30 feet to over 80 feet in two decades, and fear the 160 MW build-out will draw on it. Yotta says it uses only treated non-potable water (Down To Earth). |
| 2023–24 | Chile and Uruguay | A court ordered Google to rework its Cerrillos plan, designed to use about 7 billion litres a year, during Chile’s decade-long drought. In Uruguay, after the 2023 drought pushed Montevideo’s supply near collapse, Google dropped a 2.7-billion-litre design. Both switched to air cooling (AFP via Solar Daily). |
| 2023 | Northern Virginia, US | The world’s largest data centre cluster used close to 2 billion gallons, up 63% from 2019, and Loudoun Water still serves it mostly with potable water (EESI). |
| Dec 2022 | The Dalles, Oregon, US | Only after a newspaper lawsuit did records show Google’s water use had nearly tripled in five years (The Oregonian via WaterWatch). |
Three patterns emerge from these cases. Problems tend to arise when data centres are built in areas already facing water stress. A lack of transparency can quickly turn concerns over water use into questions of public trust, and, in many instances, companies have changed their approach only after facing court intervention, severe droughts or public scrutiny of their water disclosures.
What companies are doing now to cut freshwater use
The industry’s playbook has shifted from ‘use less’ to ‘use the right water, in the right place.’ Seven levers now do most of the work.
| Lever | How it saves freshwater | Who is doing it |
|---|---|---|
| Closed-loop, direct-to-chip liquid cooling | Coolant stays sealed in a loop that touches the chip, so nothing evaporates. | Microsoft’s 2024 AI design uses zero water for cooling during operations (Microsoft). Sify is certified for liquid cooling at Chennai, Rabale and Noida, up to about 130 kW per rack (Sify). |
| Air cooling, with water only on the hottest days | Outside air does the work; evaporation kicks in only above a set temperature. | Microsoft’s direct air cooling uses water only above 29.4°C: almost never in Northern Europe, up to 40% of the year in Phoenix (Microsoft). Google’s new Horndal, Sweden site is air-cooled (PPC Land). Nxtra uses air-based chillers at most core sites (Nxtra). |
| Recycled and non-potable water | Treated sewage or industrial water replaces drinking water in cooling. | AWS cools 24 sites with recycled wastewater and plans 120 US sites by 2030 (GeekWire). Microsoft runs on 99% non-potable water in Singapore. Nxtra’s sewage plants recycled 15,329 kL in FY25; it targets 100% wastewater recycling at hyperscale campuses. |
| Squeezing more from each litre | Smarter controls, leak detection and higher cycles of concentration in towers. | Microsoft’s WUE fell from 2.3 L/kWh in the early 2000s to 0.27 in 2025; Phoenix improved 23% in FY25 from better controls alone (Microsoft). AWS checks supply pipes for leaks and tunes cooling settings through the day (GeekWire). |
| Rainwater harvesting and reuse | Harvested rain and RO-treated blowdown feed chillers. | STT GDC India reuses cooling-tower water through RO, and its Bengaluru 3 site was India’s first IGBC Net Zero Water data centre (STT GDC India). Microsoft’s new Quebec sites expect up to 1.5 million litres of rain a year. |
| Siting and design by watershed | Cooling choice follows local water stress, decided before construction. | Equinix codified in 2023 that it will avoid evaporative cooling in high-stress areas (Equinix). Google says future cooling choices will depend on watershed conditions, favouring air or reclaimed water in stressed areas (WaterWorld). |
| Replenishment and disclosure | Funding watershed projects, and publishing site-level data. | Google targets 120% replenishment by 2030 (Trellis) and has committed over $500 million to water and reuse infrastructure (WaterWorld). AWS says it is now water positive across its direct operations in India (Amazon). |
India’s best evidence that efficiency works in hot, humid conditions comes from STT GDC India, the one large operator that publishes an externally assured WUE series.
The measures STT lists are ordinary ones: air-cooled chillers in water-scarce cities, RO reuse of cooling-tower water and rainwater harvesting. None required leaving India’s heat.
Policy is beginning to catch up with the industry’s rapid growth. Rajasthan’s 2025 Data Centre Policy, for instance, mandates wastewater recycling, zero liquid discharge and rainwater harvesting. The Central Ground Water Authority is also encouraging operators to shift towards recycled water (Analytics India Magazine). However, such measures remain the exception. No major state policy yet mandates water-use disclosures through a centralised reporting system, leaving significant gaps in transparency and accountability (Down To Earth).
The verdict: Real, local and fixable
The reality is that data centre water use is large, rising and mostly invisible, because two-thirds of it sits at the power plant. The myth is that every chat drains a bottle, or that the industry is emptying the planet. What decides the harm is where a site is built, what water it draws and how it is cooled.
A campus on treated wastewater with closed-loop cooling is close to a non-issue. An evaporative campus on groundwater in a stressed basin is a real problem, whatever its global replenishment pledge says.
For India, three steps would settle most of the argument:
- Make disclosure mandatory and comparable: Site-level withdrawal, consumption, source and WUE, reported through BRSR and independently assured.
- Default to non-potable water in stressed districts: Treated wastewater, air or closed-loop cooling, and no fresh groundwater in critical blocks.
- Put water into the approval: Large campuses should face water-stress assessments and public hearings, and cleaner power cuts the hidden grid water too.
Worth watching next: The court cases over the Visakhapatnam hub, the first FY26 disclosures from Nxtra and CtrlS, and whether India’s capacity really nears 7 GW by 2030.
Sources
Global reports and company disclosures
- DOE: Data centers consumed 4.4% of US power in 2023 — DatacenterDynamics, on the LBNL 2024 report
- A shadow water problem: AI’s power demand shifts consumption upstream — TechTarget, Sep 2026
- The hidden impacts of AI data centres on water, climate and power costs — Daily Maverick, Feb 2026 (IEA figures)
- Artificial intelligence is gobbling up water it can’t replace — Engineers Ireland (from The Conversation), Jul 2025 (IEA 2030 projection)
- Data centre water consumption could triple to 644 billion litres by 2030 — Down To Earth, Aug 2026 (Rystad Energy)
- Making AI Less “Thirsty” — Li, Yang, Islam and Ren, arXiv v5, Mar 2025
- ChatGPT consumes more water than expected — Domus, Oct 2024
- Google says the median Gemini prompt uses 5 drops of water — The New Stack, Aug 2025
- Experts accuse Google of downplaying AI water use — Neowin
- Google’s Environmental Report splits the AI story in two — The Heart of Tech, Jul 2026
- Google’s AI expansion weighs heavily on climate goals — Trellis, Jun 2026
- Google cuts operational emissions 2% as AI supply chain emissions rise — PPC Land, Jul 2026
- Google expands water stewardship efforts — WaterWorld, Jun 2026
- Microsoft claims 2025 water replenishment milestone — Facilities Dive, Jun 2026
- Inside Microsoft’s two-decade push to cut water intensity — Microsoft, Jun 2026
- AWS sustainability and Spotlight on water — Amazon
- Amazon expands use of wastewater to cool its cloud — GeekWire, 2025
- How data centers use water — Equinix, Sep 2024
- How datacenters use water — The Register, Jan 2025
- Balancing Bits and Drops — Talukder et al., ACM e-Energy, Jun 2026
- In Hot Water: Challenges with Measuring Data Center Water Usage — Stanford Undergraduate Research Journal, 2026
- Data centers and water consumption — EESI, Jun 2025
- Data center water use — MOST Policy Initiative, Apr 2026
- Google’s water use soaring in The Dalles — The Oregonian via WaterWatch, Dec 2022
- Drought forces Big Tech to rethink thirsty LatAm data centers — AFP via Solar Daily, Oct 2024
India
- What data centre giants aren’t saying about their water use — Down To Earth, Nov 2025
- Data centres are rising in water-scarce regions, and locals are paying the price — Down To Earth, Nov 2025
- Thirsty data centres, thin regulation — Down To Earth, Aug 2026
- Integrated Report 2025-26 and Sustainability Report 2024-25 — Sify Technologies
- ESG Report FY2025 — STT GDC India, Mar 2026
- Sustainability Report 2025 — Nxtra by Airtel, Aug 2025
- Data centre sector research summary — ICRA, Sep 2025
- Scaling India’s Data Centre Ecosystem — CEEW and SYSTEMIQ, Feb 2026
- India’s AI boom could double data centre water consumption by 2030 — Analytics India Magazine, Jun 2026
- India’s data centres grow fast, water risks grow faster — Analytics India Magazine, Apr 2026
- India’s data centre capacity to reach 1.8 GW by 2027 — JLL, Apr 2025
- India’s data centre infrastructure reaches 1.8 GW — The Realty Today, citing Savills, Jul 2026
- Cooling appliances now drive India’s household electricity use — Down To Earth, May 2026
- India’s coal power sector continues to disregard water norms — Down To Earth, Jun 2021
- India bets on data centres even as water and energy concerns mount — Mongabay-India via Scroll, May 2026
- Google’s India AI hub cleared for 2.51 GW, not 1 GW — The Next Web, citing the Guardian, Sep 2026